CONFIG Commands - 6
CONFIG COUNT
Tasking Statement
SYNTAX: CONFIG COUNT number,address,bit [,preset] [,AUTO]
PURPOSE: To define the characteristics of a software counter.
REMARKS: The CONFIG COUNT statement is the initial step in setting up a software counter. Up to eight
counters can be defined. A counter input may be any digital input.
The counter number has a range of 0 to 7. The address is the address of a parallel I/O port. The bit
parameter specifies bit 0 through 7 of that port.
The optional preset parameter is only used when you want an interrupt at a specified number of
counts. When the optional AUTO parameter is specified, the counter will automatically reset to zero
when the preset is reached.
For additional information see the Multitasking Chapters.
RELATED: ON COUNT, START COUNT, STOP COUNT, RESUME COUNT
EXAMPLE: 10 CONFIG COUNT 4,32,2,5000
This configures counter 4 at address 32, and bit 2 with a preset count of 5000.